Model A2

Water-Cooled Ultra-Low Temperature Process Chiller

Alpha Series Model A2 ultra-low temperature process chiller

Cooling Capacities

oC-40-50-60-70-80
KW1612.98.44.61.8
Rated cooling capacity 8 KW at -60oC based on Syltherm XLT heat transfer fluid and condenser cooling water temperature 15oC.

Instrumentation and Controls

Setpoint range-40oC to -80oC
Temperature stability+/- 1.0oC
CertificationUL 508A Industrial control panel
Control panel enclosureNEMA 4X Stainless steel
Operator interface4″ Color touch-screen graphic display
Control systemProgrammable logic controller (PLC)
Alarms monitoredTemperatures, pressures, equipment status
CommunicationsModbus protocol, RS-232 and RS-485 serial interfaces
Temperature sensorInternal Pt100 RTD
Tank level indicationElectronic analog level transmitter

Refrigeration System

System type2-Stage cascade refrigeration cycle
High stage refrigerantR404A
Low stage refrigerantR23
High stage compressor4-Cylinder semi-hermetic reciprocating compressor
Low stage compressor2-Cylinder semi-hermetic reciprocating compressor
Condenser cooling water 35 KW at 15oC
CondenserWater-cooled shell and tube heat exchanger
Cascade condenserStainless steel brazed plate heat exchanger
EvaporatorStainless steel brazed plate heat exchanger

Recirculation System

Secondary refrigerantSyltherm XLT, Dynalene HF-LO, or similar heat transfer fluid
Expansion tank25 Gallon stainless steel reservoir
PipingWelded stainless steel piping and valves
Pump typeMagnetically coupled external gear positive displacement pump
Rated pump flow10.75 GPM
Maximum pressure45 PSI

Electrical Power Requirements

33 Full Load Amps (FLA)460 Volts3-Phase60 Hz
66 Full Load Amps (FLA)208-230 Volts3-Phase60 Hz
Voltage shall be specified

Physical Parameters

Materials of constructionStainless steel frame and cabinet, with 4 casters
Dimensions (L x W x H)34 x 72 x 72 (in.)
Weight1,850 lbs.
Cooling water pipe fittings1-1/4″ MNPT
Recirculation pipe fittings3/4″ FNPT

System Warranty

12 MonthsParts and Labor